Condenser evaporator filled with nitrogen protection welding process

Nitrogen filled protection welding
 

 

Nitrogen-filled protection

Nitrogen filling:
Open the nitrogen cylinder valve and adjust the pressure reducing valve to the appropriate nitrogen pressure (generally controlled at 0.2-0.3kgf/cm²).
Insert the gas tube into one end of the condenser or evaporator copper tube to ensure that nitrogen covers the welding area adequately.
Weld while filling nitrogen to ensure a continuous supply of nitrogen during the welding process to isolate oxygen from the air.


Welding operation:
Use a special welding gun for welding, and there should be a vent in the welding gun so that nitrogen can be sprayed to protect the welding area.
During the welding process, the flame size and direction should be controlled to ensure that the flame always covers the contact and avoids air entry.
After welding is complete, close the nitrogen cylinder valve and pressure reducing valve, and properly place the nitrogen protective welding fixture and gas tube.

Pressure retention and detection

Pressure holding test:
After the welding is complete, the condenser or evaporator should be tested for pressure retention. Fill the copper pipe with nitrogen at a certain pressure (for R410A refrigerant, keep the pressure in the pipe at 40 kg, and for R22 refrigerant, keep the pressure in the pipe at 20 kg), and slowly drive the nitrogen into the copper pipe through the low-pressure process port.
If the system is equipped with a liquid solenoid valve, it is necessary to open the solenoid valve with power and install a positive pressure gauge at the high pressure process port to monitor the pressure.
The pressure holding time depends on the type of refrigeration equipment, the general household multi-connection is 8 hours, and the cold storage system is at least 12 hours.


Pressure detection:
During the pressure holding process, the reading of the pressure gauge should be checked regularly to ensure that the pressure is stable without leakage.
Pay attention to the impact of ambient temperature changes on nitrogen pressure, and adjust the pressure if necessary.

 

 