Analysis Of Influence Factors On Heat Transfer Performance Of Parallel Flow Heat Exchanger
Leave a message
1 Influence of the face wind speed on the air side heat transfer coefficient
Effect of different face wind speed on air side heat transfer coefficient. When the fin height is 6mm and other parameters are kept constant, the air side heat transfer coefficients corresponding to them are 142w/ (m2k) and 268w/ (m2k) when the face wind speed is 1.5m/s and 4.5m/s, respectively. It can also be seen from Figures 2 to 3 that, under the same conditions, the heat transfer coefficient of the air side increases with the increase of the face wind speed, and the heat transfer coefficient of the air side grows faster in the low speed zone. However, there is a critical wind speed for condensers with different structures. When the wind speed exceeds the critical wind speed, the air side resistance will increase rapidly, and the heat transfer tends to a constant value. In the optimization design of parallel flow condenser, its structure should be selected reasonably, so that its face wind speed is lower than the critical wind speed.
Effect of tooth height on air side heat transfer coefficient
When the face wind speed is 3m/s and other structural parameters are unchanged, the heat transfer coefficient of the air side is 257w/ (m2k) when the tooth height is 5mm. When the tooth height increases to 8mm, the heat transfer coefficient on the air side also decreases to 158w/ (m2k). When the parallel flow heat exchanger is under the same flat tube width, flat tube number, face wind speed, tooth thickness and tooth spacing, reducing the tooth height can reduce the hydraulic diameter of the air side, increase the flow velocity of the air flow through the tooth, so as to improve the heat transfer coefficient of the air side and improve the heat transfer of the heat exchanger. However, due to the increase of heat transfer, the refrigerant flow rate increases, while the number of flat tubes remains unchanged, so that the refrigerant pressure drop increases and the temperature difference decreases.
3. Influence of tooth spacing on air side heat transfer coefficient
In parallel flow heat exchangers, the spacing of tooth blades affects not only the hydraulic diameter of the air side, but also the air flow efficiency. It shows that when the face wind speed is 1.5m/s and other structural parameters are unchanged, the heat transfer coefficient of the air side is 109w/ (m2k) when the tooth spacing is 1.2mm. When the spacing between the teeth increases to 1.8mm, the heat transfer coefficient on the air side decreases to 99w/ (m2k). Reducing the distance between the teeth can reduce the hydraulic diameter of the air side, increase the heat transfer area per unit length of the heat exchanger, improve the heat transfer coefficient of the air side, and improve the heat transfer performance of the heat exchanger.
Effect of shutter Angle on air side heat transfer coefficient
If most of the air flows through the shutters of the tooth plates, the heat transfer between most of the air and the tooth plates is considered effective; If most of the airflow flows directly through the passage without the shutters of the teeth, the heat transfer between most of the airflow and the teeth is considered to be ineffective. Therefore, the heat transfer coefficient on the air side also has a great relationship with the Angle of the blinds.
The heat transfer coefficient on the air side also increases from 127w/ (m2k) to 177w/ (m2k) when the Angle of the blinds changes from 18° to 33° when the face wind speed is 3m/s. Therefore, under appropriate process conditions, the Angle of the blinds can be appropriately increased in order to improve the heat transfer coefficient on the air side.
Effect of other factors on performance of parallel flow heat exchanger
The performance of parallel flow heat exchanger is affected by the spacing of blinds, the shape of flat tube microchannel and the number of flat tube microchannel holes. When the face wind speed is 3m/s, the heat transfer coefficient on the air side increases from 154w/ (m2k) to 158w/ (m2k) when the shutter spacing increases from 0.8mm to 1.3mm, and the change is not large. It indicates that the change of the spacing of the blinds has little effect on the air-side heat transfer coefficient.
Different shapes of flat tube microchannels affect the heat transfer performance of parallel flow heat exchangers. The heat transfer performance of the triangular microchannel is worse than the rectangular one, and the pressure loss is larger than the rectangular one. For the same flat tube width, the heat transfer performance of the porous triangular microchannel is lower than that of the porous rectangular microchannel. The outlet pressure of the refrigerant in the porous triangular microchannel is 2.1 ~ 9.9 lower than that in the porous rectangular microchannel, and the heat transfer is reduced by 17 ~ 25. Although the porous triangular microchannel increases the refrigerant wetting perimeter under the same flat tube width, the effective heat transfer area does not increase, so the heat transfer performance of the porous triangular microchannel is lower than that of the porous rectangular microchannel. Therefore, porous rectangular microchannels are mainly used in current parallel flow heat exchangers. At the same time, the more the number of micro-channel holes in the flat tube, the better the heat transfer performance of the heat exchanger.
Conclusion
① The heat transfer coefficient of the air side increases with the increase of the face wind speed. However, in order to reduce the noise and control the face wind speed within the critical wind speed range, according to different parallel flow heat exchanger structures, the face wind speed should be controlled within a reasonable range.
② Under certain conditions, reducing the height and spacing of the teeth can reduce the hydraulic diameter of the air side, improve the heat transfer coefficient of the air side, so as to improve the heat transfer performance of the heat exchanger.
(3) Other factors such as the Angle and spacing of the shutters also have a certain influence on the heat transfer coefficient of the air side, but the influence is small. At the same time, the shape of the flat tube microchannel and the number of holes in the flat tube microchannel also affect the flow and heat transfer performance of the refrigerant in the microchannel