Refrigeration unit condenser evaporator working principle explanation
Leave a message
The evaporator is one of the four parts of the refrigeration unit, which is a heat exchanger. The working principle of the refrigeration unit is to use the evaporation method to evaporate the refrigerant (boiling), absorb the heat of the refrigerant, and achieve the purpose of refrigeration. The evaporator is the cold output equipment of the refrigeration unit. The evaporator is mainly composed of a heating chamber and an evaporation chamber. The heating chamber mainly provides the heat required for the evaporation of the liquid to promote the boiling and vaporization of the liquid. When the evaporation chamber is in a larger space after gasification, the liquid can be separated from the steam by its own condensation or the role of the defroster.
The evaporator is a heat exchanger that allows the low-temperature liquid refrigerant to exchange heat with the medium that needs to be cooled.
The types of evaporators are: full liquid evaporator, dry evaporator, circulating evaporator, spray evaporator.
Because of the different role of the refrigeration unit, the type of evaporator used is also different, and then the commonly used full liquid evaporator and dry evaporator as an example, to tell you about their respective roles.
1. Full liquid evaporator: Its function is that when the refrigerant is passed in the heat exchange tube, the refrigerant will completely immerse the heat exchange tube, and it will evaporate outside the heat exchange tube after absorbing heat. There are many pin-shaped holes on the outer surface of the heat exchange tube, and spiral threads on the surface of the tube, which will strengthen the boiling outside the tube and the heat transfer inside the tube. The advantage of the full liquid evaporator is that the heat transfer coefficient is higher than that of the dry evaporator. Its disadvantage is that the refrigerant charge amount is large, the cost is high, the evaporator cylinder will accumulate oil, and there must be reliable oil return measures.
2. Dry evaporator: Its role is that when the refrigerant passes in the heat exchange tube, the refrigerant will run outside the heat exchange tube, and the heat transfer efficiency of this type of heat exchanger is relatively low. Its advantage is that it is easy to return oil and easy to control, and the filling amount of refrigerant is about 1/2 to 1/3 of the filling amount of the full-liquid unit, which is more economical.