Cleaning method of wire tube condenser
Leave a message
Mechanical descaling
Method overview:
Especially suitable for vertical shell and tube condenser.
A bevel gear scraper connected with a flexible shaft pipe washer is used to rotate and roll the scale in the riser of the condenser from top to bottom.
Steps:
Drain the refrigerant from the condenser.
Close all valves connecting the condenser to the refrigeration system.
The cooling water of the condenser is supplied normally.
Select the appropriate diameter of the hob, the diameter of the hob selected for the first descaling is smaller than the inner diameter of the cooling pipe to prevent damage to the pipe wall, and then choose a hob close to the inner diameter of the cooling pipe for the second descaling.
Using circulating cooling water to cool the heat generated by the friction between the scraper and the pipe wall, at the same time, the dirt such as scale and rust removed will be washed into the pool.
Chemical pickling and descaling
Method overview:
Suitable for vertical and horizontal shell and tube condensers.
Use the prepared weak acid detergent to clean the condenser and make the scale fall off.
Steps:
Prepare the descaling solution in the pickling tank.
Close the inlet valve, outlet valve, balance pipe valve, mixed gas valve, oil discharge valve and other valves on the condenser to stop the work of the condenser cooling pump.
Start the pickling pump, make the detergent solution circulate in the condensing tube of the condenser for 24 hours, check the scale shedding situation and then determine whether to continue cleaning.
After the pickling pump is stopped, use a round steel brush to pull the brush back and forth in the tube wall of the condensing pipe, and rinse the dirt and rust with clean water.
Then clean the detergent solution remaining in the pipe repeatedly with clean water until it is completely clean.